Acme Electric TP530193S

Acme Electric TP530193S Air Colled/Dry Distribution Transformer, 240/480 VAC Primary, 120/240 VAC Secondary, 37.5 kVA Power Rating, 60 Hz, 1 ph Phase
NEMA Transformers
6841311 TP530193S
Acme Electric
$0.00 / ea

  • Connection Type: Wire Lead
  • Dimensions: 19.37 in L x 24.39 in W x 25.5 in H
  • Efficiency: 98.22
  • Enclosure Type: NEMA 2
  • Frequency Rating: 60
  • Housing Material: Steel
  • Insulation: 200
  • Maximum Amperage Rating: 100/200/400
  • Mounting Type: Floor
  • Phase: 1
  • Power Rating: 37.5
  • Primary Voltage: 240/480
  • Secondary Voltage: 120/240
  • Temperature Rating: 150
  • Type: Air Colled/Dry
Acme Electric Distribution Transformer, Air Colled/Dry, 240/480 VAC Primary, 120/240 VAC Secondary, 37.5 kVA, 60 Hz, 1 ph, 100/200/400 A Maximum, Wire Lead, Floor Mount, 200 deg C, NEMA 2, 150 deg C, 98.22 % Efficiency, Steel Housing, 19.37 in L x 24.39 in W x 25.5 in H
  • Features
  • Ground studs for use with non-metallic conduit
  • Quiet operation with sound levels well below NEMA standards
  • Electrostatic shield for enhanced protection
  • Encapsulated core and coil
  • Ventilated core and coil
  • Extra large wiring compartment for easier installation and cooler case temperatures
  • NEMA standard busbar terminals, no special tools needed to make clearly marked connections, tap changing easily accomplished with jumpers
  • Aluminum windings for increased insulation life, cooler operation, lower losses
  • Noise and vibration isolating pads standard to assure quiet operation
  • Large permanently legible nameplates on front
  • Single phase units can be banked for 3-phase service
  • All units have ground studs for use with non-metallic conduit
  • 3.65% at 100% pF regulation
  • 145 W no load losses
  • 821 W full load
  • Energy efficient
  • Air cooled/dry cooling
  • Four windings
  • Aluminum, two primary winding, two winding secondary
  • 200 A for 240 VAC, 100 A for 480 VAC primary, 400 A for 120 VAC secondary