Acme Electric TP530193S
Acme Electric TP530193S Air Colled/Dry Distribution Transformer, 240/480 VAC Primary, 120/240 VAC Secondary, 37.5 kVA Power Rating, 60 Hz, 1 ph Phase
NEMA Transformers
6841311
TP530193S
Acme Electric
$0.00
/ ea
- Connection Type: Wire Lead
- Dimensions: 19.37 in L x 24.39 in W x 25.5 in H
- Efficiency: 98.22
- Enclosure Type: NEMA 2
- Frequency Rating: 60
- Housing Material: Steel
- Insulation: 200
- Maximum Amperage Rating: 100/200/400
- Mounting Type: Floor
- Phase: 1
- Power Rating: 37.5
- Primary Voltage: 240/480
- Secondary Voltage: 120/240
- Temperature Rating: 150
- Type: Air Colled/Dry
Acme Electric Distribution Transformer, Air Colled/Dry, 240/480 VAC Primary, 120/240 VAC Secondary, 37.5 kVA, 60 Hz, 1 ph, 100/200/400 A Maximum, Wire Lead, Floor Mount, 200 deg C, NEMA 2, 150 deg C, 98.22 % Efficiency, Steel Housing, 19.37 in L x 24.39 in W x 25.5 in H
- Features
- Ground studs for use with non-metallic conduit
- Quiet operation with sound levels well below NEMA standards
- Electrostatic shield for enhanced protection
- Encapsulated core and coil
- Ventilated core and coil
- Extra large wiring compartment for easier installation and cooler case temperatures
- NEMA standard busbar terminals, no special tools needed to make clearly marked connections, tap changing easily accomplished with jumpers
- Aluminum windings for increased insulation life, cooler operation, lower losses
- Noise and vibration isolating pads standard to assure quiet operation
- Large permanently legible nameplates on front
- Single phase units can be banked for 3-phase service
- All units have ground studs for use with non-metallic conduit
- 3.65% at 100% pF regulation
- 145 W no load losses
- 821 W full load
- Energy efficient
- Air cooled/dry cooling
- Four windings
- Aluminum, two primary winding, two winding secondary
- 200 A for 240 VAC, 100 A for 480 VAC primary, 400 A for 120 VAC secondary