Appleton ESUM75

Appleton Unilets ESUM75 Dust-Ignitionproof Explosionproof Conduit Sealing Fitting, 3/4 in, For Use With IMC/Threaded Rigid Metal Conduit, Malleable Iron, Tri-Coated
Channel-Strut Accessories
418541 ESUM75
Appleton
$0.00 / ea

  • Dimensions: 3.13 in L x 2.94 in W
  • Finish: Tri-Coated
  • Material: Malleable Iron
  • Mounting Type: Surface
  • Size: 3/4
  • Suitable For Use With: IMC/Threaded Rigid Metal Conduit
  • Type: Dust-Ignitionproof Explosionproof
Explosionproof Rigid/IMC Conduit Seal, Turning Radius 1.25 Inch, Trade Size 3/4 Inch, Connection Type Male, Female, Material Zinc Electroplated Chromate Epoxy Powder Coated Malleable Iron, Mounting Position Horizontal/Vertical, Enclosure Class I Div 1 and 2 Group C D, Class II Div 1 and 2 Group E F G, Class III, Approval UL 886/E10444, CSA C22.2, Size 3.13 Inch L x 2.94 Inch W, Constructional Feature Explosionproof, Dust-Ignitionproof, Raintight, Used On Threaded Rigid/IMC Metal Conduit, Includes Removable Male Nipple
  • Features
  • Smooth, rounded integral bushing in each hub protects conductor insulation
  • Accurately tapped, tapered hub threads for tight, rigid joints and ground continuity
  • Removable nipple in male sealing fitting may be used interchangeably in top or bottom hub
  • For sealing vertical or horizontal conduit
  • Pouring spout rotates 90 deg
  • Removable cover provides full access for damming 1/2 to 1 in sizes have threaded cover openings for damming
  • 1-1/4 in turning radius
  • Triple coat of zinc electroplate, chromate and epoxy powder coated finish
  • Prevent passage of gases, vapors or flames from one portion of conduit system to another
  • Restrict any explosion to the sealed off enclosure
  • Required in class I, Division 1 and 2 locations within 18 in of enclosures containing apparatus that may cause arcs, sparks or high temperatures
  • Required in class I, Division 1 and 2 locations where 2 in or larger conduit enters enclosure, fitting housing terminals, splices or taps
  • Required in class I, Division 1 and 2 locations at the boundary where conduit leaves classified location
  • Required in class I, Division 1 and 2 locations where two or more enclosures are connected by 36 in or less conduit
  • Seal must be located within 18 in of either enclosure