Midwest GE R101CB6HP Back-to-Back Metered Ringless Head Post, 120/240 VAC, 100 A, 1 ph Phase, 6 AWG to 350 kcmil, 12 to 2 AWG Wire, NEMA 3R Enclosure
Enclosure Back Panels and Covers
5324381 R101CB6HP
Midwest
$0.00 / ea

  • Amperage Rating: 100
  • Circuit Breaker Type: CB120/CB2100
  • Enclosure Type: NEMA 3R
  • Feed Type: Underground/Loop
  • Material: G90 Galvanized Steel
  • Mounting Type: Surface
  • Phase: 1
  • Type: Back-to-Back Metered Ringless
  • Voltage Rating: 120/240
  • Wire size: 6 AWG to 350 kcmil, 12 to 2 AWG
National Electric Code requires electrical distribution equipment to be rated as Service Entrance, wherever electrical power enters a building or other structure. Service entrance products are typically utilized on single-family residences and mobile homes. Midwest Electric offers a broad range of surface mount and pedestal units, factory assembled and wired. Pedestal units come standard with loop feed lugs to reduce installation time and labor expense. Service Entrance equipment is made of heavy, galvanized G-90 steel, preventing corrosion and fading.
  • Features
  • 2-head
  • 3 additional breaker space per head
  • Series wiring configuration
  • LC55N1 load center
  • Provision for field installation circuit protection
  • Load centers are provided with copper bus, 22 kAIC bus bracing and 100% neutral terminations, feed-through lugs provided on load centers with main breaker
  • 320 a continuous duty meter socket
  • All terminals accept copper or aluminum wire for added installation flexibility
  • Utility meter socket compartment has barrier from main circuit breakers for utility power protection
  • Factory installed flange for easy semi-flush or surface installation
  • Durable polyester powder coat finish resists chipping and fading
  • Branch circuit accept combinations up to 200 a
  • Line side 1/2 in stud termination provided, however, crimp-on/connector lug not provided by Midwest
  • 10000 AIC interrupt rating