Eaton Bussmann Inc. TCF17-1/2
Bussmann Low-Peak™ CUBEFuse™ TCF17-1/2 Current Limiting Inrush Current Withstand Time Delay Fuse, 17.5 A, 600 VAC/300 VDC, 100/300 kA Interrupt, Class: CF, Square Body
                                 Class CF Fuses 
                                
                            
                                    568340
                                        TCF17-1/2
                                
                                
                                        
                                        Eaton Bussmann Inc.
                                
                            
                                
                                
                                                                        
                                            
                                            $0.00
                                        
                                        
                                            / ea
                                        
                                                                    
                        
- Amperage Rating: 17.5
 - Body Size: 1.88 in L x 0.75 in W x 1 in H
 - Body Type: Square
 - Class: CF
 - Element: Dual
 - Interrupt Rating: 100/300
 - Material: Glass Filled Polyethersulfone
 - Mounting Type: Chassis/DIN Rail
 - Response Time: 10 s at 500%
 - Series: TCF
 - terminal type: Blade
 - Type: Current Limiting Inrush Current Withstand
 - Voltage Rating: 600 VAC/300 VDC
 
Eaton Bussmann series TCF fuse, 17.5 A, 60 Hz, 50 Hz, Dual, CF, Black, With Indicator, Blade end, Time delay, 10 sec at 500%, 300 kAIC at 600 V,100 kAIC at 300 Vdc, Glass filled PES, 35 mm DIN rail,Chassis, 600 V, 300 Vdc
                        - Features
 
- The world's first finger safe power fuse system
 - Smallest footprint of any class fuse including class J, CC, T and RK
 - The indicating version features easyID™ open fuse technology for faster troubleshooting and reduced downtime
 - Faster response to damaging faults to help reduce destructive thermal and magnetic forces
 - True dual element fuse construction with a minimum of 10 s time delay at 500% of rating
 - Long time delay minimizes nuisance circuit openings due to temporary overloads and transient surges
 - High 300 kA interrupt rating safely interrupts virtually any fault
 - No venting of arc or molten metal and gases during opening
 - Robust cycling and inrush current withstand
 - Low let through currents under fault conditions
 - Provides type 2 "no damage" in protection for IEC® motors starters when properly sized
 - Easy selective co-ordination with any other Bussmann series Low-Peak™ class CC, J, L or RK1 fuse with simple 2:1 amp ratio between upstream and downstream fuses